C01124 | sync-pll increment, C01125 | service code, C01126 | service code – Lenze E94ARNE Regenerative power supply User Manual

Page 326: C01124, Defines the increment

Advertising
background image

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C01124

326

L

EDS94ARNExxxx EN 2.3 - 06/2014

C01124

C01125

C01126

Parameter | Name:

C01124 | Sync-PLL increment

Data type: UNSIGNED_8

Index: 23451

d

= 5B9B

h

If the cycle times of the synchronisation signal and the phase-locking loop (PLL) deviate from each other, this setting

defines the increment by which the phase-locking loop can be corrected.

• For the system bus (CANopen) as synchronisation source, the recommended time setting in the case of occurring

deviations is 109 ns.

"CAN on board" system bus: sync telegram

Selection list

(Lenze setting printed in bold)

1 7 ns
2 15 ns
3 23 ns
4 31 ns
5 39 ns
6 46 ns
7 54 ns
8 62 ns
9 70 ns

10 78 ns
11 85 ns
12 93 ns
13 101 ns
14 109 ns
15 117 ns
16 125 ns
17 132 ns
18 140 ns
19 148 ns
20 156 ns
21 164 ns
22 171 ns
23 179 ns
24 187 ns
25 195 ns
26 203 ns
27 210 ns

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C01125 | Service code

Data type: UNSIGNED_32

Index: 23450

d

= 5B9A

h

This code is used internally by the device and must not be overwritten by the user!

Parameter | Name:

C01126 | Service code

Data type: UNSIGNED_32

Index: 23449

d

= 5B99

h

This code is used internally by the device and must not be overwritten by the user!