0x00870008, 0x00870002, 0x00870003 – Lenze E94ARNE Regenerative power supply User Manual

Page 235: 0x00890000, 0x00880000, Diagnostics & fault analysis error messages

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

235

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

CAN on board RPDO3: Telegram not received or faulty [0x00870002]

CAN on board RPDO4: Telegram not received or faulty [0x00870003]

CAN on board PDO manager: Configuration is faulty [0x00870008]

CAN on board SDO server: Faulty configuration [0x00880000]

CAN on board SDO client: Faulty configuration [0x00890000]

Response (Lenze setting printed in bold)

Setting:

C00591/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: CAN-IN 3 error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00591/4

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: CAN-IN 4 error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: CAN-PDO configuration error

• Faulty project download.

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Mapping variables have incorrect CANopen indexes

according to DS405.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: A configuration error has occurred in the

CAN SDO server.

• Faulty project download.

• Invalid SDO server settings according to DS301V402

in the Engineer or PLC Designer.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: A configuration error has occurred in the

CAN SDO client.

• Faulty project download.

• Invalid SDO client settings according to DS301V402 in

the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Advertising