C00064 | device utilisation (ixt), C00065 | ext. 24-v voltage, C00068 | capacitor temperature – Lenze E94ARNE Regenerative power supply User Manual

Page 278: C00069 | cpu temperature, C00070 | dc bus voltage ctrl. gain, C00071 | dc bus voltage ctrl. reset time, C00075 | current controller gain, Ic filter nameplate (enp), C00070, C00071

Advertising
background image

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00064

278

L

EDS94ARNExxxx EN 2.3 - 06/2014

C00064

C00065

C00068

C00069

C00070

C00071

C00075

Parameter | Name:

C00064 | Device utilisation (Ixt)

Data type: UNSIGNED_32

Index: 24511

d

= 5FBF

h

Device utilisation during the last 180 seconds

• C00064 > 100 % activates error (OC5).

• Error reset only possible if C00064 < 95 %.
Display range

(min. value | unit | max. value)

0

%

250

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00065 | Ext. 24-V voltage

Data type: INTEGER_32

Index: 24510

d

= 5FBE

h

Display range

(min. value | unit | max. value)

0.0

V

1000.0

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00068 | Capacitor temperature

Data type: INTEGER_32

Index: 24507

d

= 5FBB

h

Display range

(min. value | unit | max. value)

-200

°C

200

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00069 | CPU temperature

Data type: INTEGER_32

Index: 24506

d

= 5FBA

h

Display range

(min. value | unit | max. value)

-200

°C

200

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00070 | DC bus voltage ctrl. gain

Data type: UNSIGNED_32

Index: 24505

d

= 5FB9

h

Note: This parameter is only effective in closed-loop operation (in preparation).
Setting range

(min. value | unit | max. value)

Lenze setting

0.00000

Nm/rpm

20000.00000 0.00400 Nm/rpm

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100000

Parameter | Name:

C00071 | DC bus voltage ctrl. reset time

Data type: UNSIGNED_32

Index: 24504

d

= 5FB8

h

Note: This parameter is only effective in closed-loop operation (in preparation).
Setting range

(min. value | unit | max. value)

Lenze setting

1.0

ms

6000.0 50.0 ms

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00075 | Current controller gain

Data type: UNSIGNED_32

Index: 24500

d

= 5FB4

h

Note: This parameter is only effective in closed-loop operation (in preparation).
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

V/A

750.00 30.00 V/A

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100

Advertising