9400 regenerative power supply module | Parameter setting

Regenerative power supply module application

Assignment of the I/O terminals

Display elements

State bus

Analog outputs

Related topics:

Analog outputs

( 92)

Digital inputs

( 94)

Digital outputs

( 95)

"State bus" monitoring function

( 96)

LED status displays for the device state

( 188)

Note!

"Ready for regenerative feedback" status message via digital output DO1:
• If one of the conditions listed in the table for digital output DO1 is not met

anymore, the digital output DO1 is reset to LOW level.

Conditions for returning to the "ready for regenerative feedback" state:
• If a mains failure has been detected, the mains voltage has to be applied for

at least two complete periods after mains recovery, before the digital output

DO1 is reset to HIGH level.

• If a short circuit or earth fault has occurred, the device is ready for operation

again after approx. 2 s, i.e. after this time the digital output DO1 is

automatically reset to HIGH level.

• The device utilisation evaluation has a hysteresis of 5 %. This means that the

device utilisation (

C00064

) must drop to < (

C00123

- 5 %) before the digital

output DO1 is reset to HIGH level.

User LED

Signal (Lenze setting)

Signal configuration

"Ready for regenerative feedback" state

• See description for digital output DO1.

C03100/5

Terminal

Signal (Lenze setting)

Signal configuration

X2

SB

FALSE

C03100/6

Terminal

Signal (Lenze setting)

Signal configuration

X3

AO1

0 %

C03110/1

AO2

0 %

C03110/2