1 parameter setting, Parameter setting – Lenze E94ARNE Regenerative power supply User Manual

Page 116

Advertising
background image

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Process data transfer

116

L

EDS94ARNExxxx EN 2.3 - 06/2014

6.6.5.1

Parameter setting

Short overview: parameters for synchronisation via sync telegram

Sync source

C01120

serves to select the source of the synchronisation signals. There can always be only

one source for synchronising the nodes.

Sync cycle time
The sync cycle time, which can be set in

C01121

, is the time interval with which the internal

phase-locking loop (PLL) expects the sync signals. It must be set appropriately with regard

to the cycle of the synchronisation source selected in

C01120

.

Example: For the system bus the interval between two synchronisation signals has been

set with 2 ms. If the system bus is to be used as synchronisation source, a sync cycle time

of 2000 μs has to be set in

C01121

.

Parameter

Information

Lenze setting

Assignment

Value Unit

Sync

master

Sync

slave

C00367

CAN SYNC Rx identifier

128

C00368

CAN SYNC Tx identifier

128

C00369/1

CAN SYNC transmit cycle time

0 ms

C01120

Sync source

OFF

C01121

Sync cycle time

1000 μs

C01122

Sync phase position

400 μs

C01123

Sync tolerance

0 μs

C01124

Sync-PLL increment

109 ns

C01130

Sync application cycle

1000 μs

Note!

If the synchronisation is carried out via the system bus, only integer multiples of

1000 μs make sense for the setting in

C01121

.