9400 regenerative power supply module | Parameter setting

Device interface

Display of output and regenerated energy

88

L

EDS94ARNExxxx EN 2.3 - 06/2014

4.6

Display of output and regenerated energy

This function is available from software version V2.0 onwards!

The following parameters display the energy of the regenerative power supply module

output at the DC side and the energy fed back to the mains:

The display values are stored in the memory module with power failure protection and

are therefore even available after device replacements.

The display values can be reset to zero via the following device commands (

C00002

):

– 65:

Reset transmitted energy

( 61)

– 66:

Reset regenerated energy

( 62)

Parameter

Information

Lenze setting

Value Unit

C00145/1

Output energy, DC side

- kWh

C00145/2

Regenerated energy

- kWh

Highlighted in grey = display parameter

Note!

The kWh display does not completely replace a three-phase meter!