Power section is defect [0x00680001, Memory module is defect or missing [0x00680002, Safety module is defect or missing [0x00680003 – Lenze E94ARNE Regenerative power supply User Manual

Page 210: Mxi1: module changed during operation [0x00680004, Mxi2: module changed during operation [0x00680005, 0x00680002, 0x00680004, 0x00680005, 0x00680001, 0x00680003

Advertising
background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

210

L

EDS94ARNExxxx EN 2.3 - 06/2014

Power section is defect [0x00680001]

Memory module is defect or missing [0x00680002]

Safety module is defect or missing [0x00680003]

MXI1: Module changed during operation [0x00680004]

MXI2: Module changed during operation [0x00680005]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Operating system could not identify the power section. Mains switching

• Please contact Lenze if the error occurs again.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Operating system could not identify the memory

module.

Mains switching

• If the error occurs again: switch off regenerative

power supply module, unplug memory module and

plug it in again, switch on regenerative power supply

module again.

• If the error still occurs: switch off regenerative power

supply module and use a different memory module.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Operating system could not identify the safety module. Mains switching

• If the error occurs again: switch off regenerative

power supply module, unplug safety module and plug

it in again, switch on regenerative power supply

module again.

• If the error still occurs: switch off regenerative power

supply module and use a different safety module.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The extension module you have tried to plug into the

module slot MXI1 is not "hot plug" capable.

Plug in suitable module and switch mains.

• Through mains switching, the system accepts

modules without "hot plug" capability in the

following switch-on phase.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The extension module you have tried to plug into the

module slot MXI2 is not "hot plug" capable.

Plug in suitable module and switch mains.

• Through mains switching, the system accepts

modules without "hot plug" capability in the

following switch-on phase.