9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

CAN module (MXI2): Faulty emergency configuration [0x00ae0000]

CAN module (MXI2): Node guarding error 1 ... 32 [0x00af0000 ... 0x00a0001f]

CAN module (MXI2): Faulty NMT master configuration [0x00af0020]

CAN module (MXI2) RPDO1: Telegram not received or faulty [0x00b00000]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN

emergency configuration is faulty.

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN emergency settings according to

DS301V402 in the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

Setting:

C14612/1...32

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: Cyclic node

monitoring

• CAN master has not received a response to a node

guarding telegram (remote transmission request

telegram) from node 1 ... 32 within the defined time.

• Reactivate CAN node by mains switching, restart of

the regenerative power supply module,

(

C00002

="11000") or CAN reset node.

• Reparameterise the node guarding monitoring time

or switch off monitoring.

• Reset locked error status if necessary.

Tip: Save the current parameter set before mains

switching and restarting the regenerative power supply

module (

C00

002

="11").

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: A

configuration error has occurred in the network

management of the CAN master.

• Faulty download of an Engineer or PLC Designer

project.

• Invalid CAN master settings according to DS301V402

and DS405 in the Engineer or PLC Designer.

• Incorrect parameterisation of node guarding or

heartbeat.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

Setting:

C14591/1

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 1

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.