9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00388

C00388

C00390

C00391

Parameter | Name:

C00388 | CAN node guarding status

Data type: UNSIGNED_8

Index: 24187

d

= 5E7B

h

"CAN on board" system bus: node guarding protocol

Selection list

(display only)

0 Unknown
4 Stopped
5 Operational

127 Pre-operational

Subcodes

Information

C00388/1

State of node 1 ... 32

C00388/...
C00388/32

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00390 | CAN Error Register (DS301V402)

Data type: BITFIELD_8

Index: 24185

d

= 5E79

h

Mapping of the CANopen object

I-1001

(see DS301 V4.02)

"CAN on board" system bus

Value is bit-coded:

Information

Bit 0 Generic error

Currently only bit 0 and bit 4 contain the corresponding

information.

Bit 1 Current error (not used)
Bit 2 Voltage error (not used)
Bit 3 Temperature error (not used)
Bit 4 Communication error
Bit 5 Dev. prof. spec. err (not used)
Bit 6 Reserved
Bit 7 Manuf. spec. error (not used)

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00391 | CAN Emergency Object

Data type: BITFIELD_32

Index: 24184

d

= 5E78

h

Identifier of the emergency telegram

• If bit 31 of this code (0x8nnnnnnn) is set, the generation of emergency telegrams is deactivated.

• Mapping of the CANopen object

I-1014

(see DS301 V4.02).

"CAN on board" system bus

Value is bit-coded:

Information

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: Emergency stop

... ...

Bit 31 Emergency inactive/active

Read access  Write access  CINH  PLC STOP  No transfer