3 analog outputs, 1 terminal assignment/electrical data, Analog outputs – Lenze E94ARNE Regenerative power supply User Manual

Page 92: Terminal assignment/electrical data, Analog outputs ( 92)

Advertising
background image

9400 regenerative power supply module | Parameter setting

I/O terminals

Analog outputs

92

L

EDS94ARNExxxx EN 2.3 - 06/2014

5.3

Analog outputs

The regenerative power supply module is provided with 2 analog outputs which can be

used to output internal analog signals as voltage signals, e.g. for display via analog

indicating instruments.

5.3.1

Terminal assignment/electrical data

Note!

Initialisation behaviour:
• After mains switching until the start of the application, the analog outputs

remain set to 0 V.

Exception handling:
• In the case of a critical exception within the application (e.g. reset), the analog

outputs are set to 0 V.

Terminal

Use

Electrical data

X3/AO1

Voltage output 1

Level: -10 V ... +10 V

(max. 2 mA)

Resolution: 11 bits + sign

Scaling: ±2

30

≡ ±10 V

Conversion rate: 1 kHz

X3/AO2

Voltage output 2

Level: -10 V ... +10 V

(max. 2 mA)

Resolution: 11 bits + sign

Scaling: ±2

30

≡ ±10 V

Conversion rate: 1 kHz

X3/GA

Reference potential (analog ground)

GA

AO1

AO2

X3