9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

150

L

EDS94ARNExxxx EN 2.3 - 06/2014

I-1006

Setting the sync telegram cycle time.

The cycle time can be entered as "1000" or as an integer multiple of it.

When the setting "0 μs"

(Lenze setting) is selected, no sync telegram are generated.

This object is related to the Lenze code

C00369

.

I-100C

Monitoring time for node guarding.

Node guarding protocol

( 134)

The guard time is the time within which the NMT slave expects to receive the RTRs from

the NMT master.

The product of "guard time" and "life time factor" is the "node life time":

Node life time = guard time (

I-100C

) x life time factor (

I-100D

)

The "life guarding event" is initiated in the NMT slave if the slave has not been triggered

by an RTR from the NMT master within the "node life time".

When the setting "0 ms"

(Lenze setting) is selected, the monitoring function is not

supported by the slave.

This object is related to the Lenze code

C00382

.

I-100D

Life time factor for node guarding.

Node guarding protocol

( 134)

The product of "guard time" and "life time factor" is the "node life time":

Node life time = guard time (

I-100C

) x life time factor (

I-100D

)

The "life guarding event" is initiated in the NMT slave if the slave has not been triggered

by an RTR from the NMT master within the "node life time".

When the setting "0"

(Lenze setting) is selected, the monitoring function is not

supported by the slave.

This object is related to the Lenze code

C00383

.

Index:

I-1006

Name:

Communication cycle period

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Communication cycle period

0 μs

0

μs

65535000 rw

U32

Index:

I-100C

Name:

Guard time

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Guard time

0 ms

0

ms

65535 rw

U16

Index:

I-100D

Name:

Life time factor

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Life time factor

0

0

255 rw

U8