Heatsink: overtemperature [0x00770001, Filter: temperature > c00121 [0x00770002, Filter: overtemperature [0x00770003 – Lenze E94ARNE Regenerative power supply User Manual

Page 222: Cpu: temperature > c00126 [0x00770008, Cpu: overtemperature [0x00770009, 0x00770009, 0x00770008, 0x00770003, 0x00770002, 0x00770001

Advertising
background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

222

L

EDS94ARNExxxx EN 2.3 - 06/2014

Heatsink: Overtemperature [0x00770001]

Filter: Temperature > C00121 [0x00770002]

Filter: Overtemperature [0x00770003]

CPU: Temperature > C00126 [0x00770008]

CPU: Overtemperature [0x00770009]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Heatsink temperature higher than fixed limit

temperature (90 °C).

• Ambient device temperature too high.

• Dirty fan or ventilation slots.

• Check control cabinet temperature.

• Clean filter.

• Clean regenerative power supply module.

Response (Lenze setting printed in bold)

Setting:

C00584

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Filter temperature higher than variable limit

temperature (

C00121

).

• Filter too hot due to impermissibly high currents or

frequent and too long filter processes.

• Value set under

C00121

is too low.

• Check device dimensioning.

• Switch off monitoring (

C00584

="0").

• Set a higher value under

C00121

.

Response (Lenze setting printed in bold)

Setting:

C00583

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Filter temperature higher than fixed limit temperature

(155 °C).

• Filter too hot due to impermissibly high currents or

frequent and too long filter processes.

• Check device dimensioning.

• Switch off monitoring (

C00583

="0").

Response (Lenze setting printed in bold)

Setting:

C00589

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CPU temperature higher than variable limit temperature

(

C00126

).

• Ambient device temperature too high.

• Dirty fan or ventilation slots.

• Value set under C00126 is too low.

• Check control cabinet temperature.

• Clean filter.

• Clean regenerative power supply module.

• Set a higher value under

C00126

.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CPU temperature higher than fixed limit temperature

(85 °C).

• Ambient device temperature too high.

• Dirty fan or ventilation slots.

• Check control cabinet temperature.

• Clean filter.

• Clean regenerative power supply module.

Advertising