Mains voltage 10% too high [0x007b0045, Mains voltage 15% too high [0x007b0046, Filter: relay malfunction [0x007b0048 – Lenze E94ARNE Regenerative power supply User Manual

Page 230: Mains not connected [0x007b0049, 0x007b0049, 0x007b0045, 0x007b0046, 0x007c0000, 0x007c0001, 0x007b0048

Advertising
background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

230

L

EDS94ARNExxxx EN 2.3 - 06/2014

Mains voltage 10% too high [0x007b0045]

Mains voltage 15% too high [0x007b0046]

Filter: Relay malfunction [0x007b0048]

Mains not connected [0x007b0049]

Memory module: File system has been formatted [0x007c0000]

Memory module: File system has been restored [0x007c0001]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Mains voltage too high.

Check mains voltage.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Mains voltage too high.

Check mains voltage.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

There was no feedback from the relay in the filter, which

switches the inverter to the mains after a successful

charging process. Either the relay has not picked up, or

the feedback cable is defective.

• Check 24 V voltage supply of the filter.

• Check connecting cable between the filter and the

device (encoder plug).

• If the two previously mentioned items are OK, an

internal error has occurred within the filter (repair

required).

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

No mains connection.

Check mains connection.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

File system of the memory module has been formatted. - (Information only)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

File system of the memory module has been restored.

- (Information only)