Outputs – Lenze E94ARNE Regenerative power supply User Manual

Page 260

Advertising
background image

9400 regenerative power supply module | Parameter setting

Internal interfaces

LS_DriveInterface - device interface

260

L

EDS94ARNExxxx EN 2.3 - 06/2014

Outputs

Identifier

DIS code | data type

Value/meaning

DI_dnState

DINT

State

DI_bReady

BOOL

Status signal "Regenerative power supply module is ready for operation"

TRUE The regenerative power supply module is ready for operation.

DI_bFailActive

BOOL

Status signal "Fault active - acknowledgement is required"

TRUE A monitoring function with the error response "Fault" or "Quick stop

by trouble" has responded, and the regenerative power supply

module is in the device state "Fault active" or "Quick stop by trouble

active".

To quit the device state, the error must be acknowledged, e.g. via the

input DI_bErrorReset1...3.

DI_bImpActive

BOOL

Status signal "Pulse inhibit set"

TRUE Power output stages are switched to high resistance.

DI_bCInhActive

BOOL

Status signal "Controller inhibit active"

TRUE The controller inhibit is active.

DI_bWarningActive

BOOL

Status signal "Warning active"

TRUE A warning is pending in the regenerative power supply module.

DI_bUVDetected

BOOL

Status signal "Undervoltage detected"

• The threshold for this monitoring function depends on the setting under

C00173

.

TRUE Undervoltage detected in the DC bus.

DI_bOVDetected

BOOL

Status signal "Overvoltage detected"

• The threshold for this monitoring function depends on the setting under

C00173

.

TRUE Overvoltage detected in the DC bus.

DI_bMainSupplyOk

BOOL

Status signal "Voltage supply OK"

TRUE The voltage supply of the DC bus is sufficient.

DI_bReadyToSwitchOn

BOOL

Status signal "Regenerative power supply module ready to switch on"

TRUE The regenerative power supply module has completed the

initialisation and is in the "Device is ready to switch on" device state.

DI_bOperationEnabled

BOOL

Status signal "Operation enabled"

TRUE The regenerative power supply module is in the "Operation" device

state.

DI_dwErrorCode

DWORD

Error number of the current error message

Error messages ( 198)

DI_AxisData

Data structure, which contains all required machine constants.