C00143 | sampled peak power, C00144 | time stamp of sampled max. power, C00145 | energy out – Lenze E94ARNE Regenerative power supply User Manual

Page 283: Displayed in, C00143/1, Splay value, C00144/1, C00143/2, C00144/2, C00143/3

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

283

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00143

C00143

C00144

C00145

Parameter | Name:

C00143 | Sampled peak power

Data type: UNSIGNED_32

Index: 24432

d

= 5F70

h

From software version V2.0 onwards

C00144/1...3

display the elapsed-hour meter reading at which the respective peak power has been reached.

Display of peak power

Display range

(min. value | unit | max. value)

0.0

kW

10000.0

Subcodes

Information

C00143/1

Max. DC-power mot.

C00143/2

Max. DC-power reg. (+ br. chop.)

C00143/3

Max. line power reg.

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00144 | Time stamp of sampled max. power

Data type: UNSIGNED_32

Index: 24431

d

= 5F6F

h

From software version V2.0 onwards

Displays the elapsed-hour meter reading at which the respective peak power displayed in

C00143/1...3

has been

reached.

Display of peak power

Display range

(min. value | unit | max. value)

0

s

4294967295

Subcodes

Information

C00144/1

Time stamp max. DC-power mot.

C00144/2

Time stamp max. DC-power reg.

C00144/3

Time stamp max. line power

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00145 | Energy out

Data type: INTEGER_32

Index: 24430

d

= 5F6E

h

From software version V2.0 onwards

Display of transmitted and regenerated energy

Display range

(min. value | unit | max. value)

-2147483.647

kWh

2147483.647

Subcodes

Information

C00145/1

Output energy (DC)

C00145/2

Regenerated energy (AC)

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1000