9400 regenerative power supply module | Parameter setting

Regenerative power supply module application

Parameterising the brake chopper/brake resistor

24

L

EDS94ARNExxxx EN 2.3 - 06/2014

3.1.1

Setting the voltage threshold for braking operation

The voltage threshold for braking operation is set via

C00173

(mains voltage) and

C00181

(reduced brake chopper threshold). When the brake chopper threshold is exceeded in the

DC bus, the brake chopper is switched on.

3.1.2

Setting the brake chopper mode

For software versions below V2.0, the following applies:

The regenerative power supply module only feeds back to the mains and activates the

brake chopper if the inverter-side current reaches the maximum device current. If the

current is below the maximum device current and the DC-bus voltage is below the brake

chopper threshold, the brake chopper is not activated.

From software version V2.0 onwards, the following applies:

C00132

can be used to set the conditions for brake chopper activation:

Only at overvoltage:

The brake chopper is only activated if the DC-bus voltage has reached the brake

chopper threshold. This setting corresponds to the behaviour of the 9400 controller.

At overvoltage and overcurrent (Lenze setting):

This setting corresponds to the behaviour of regenerative power supply modules with

software versions below V2.0.

At overvoltage and overcurrent and overload:

With this setting, the brake chopper is used for energy consumption if a device

utilisation of 90 % is reached during feedback operation.
– The "normal" voltage thresholds for braking operation still apply.

Setting the

voltage threshold for braking operation

( 24)

– To protect the brake chopper against damage, monitoring of the Ixt utilisation is still

active.

Ixt utilisation of brake transistor

( 26)

Mains voltage selected in C00173

Effective brake chopper threshold

230 V

390 V - value in

C00181

(0 ... 100 V)

400/415 V

725 V - value in

C00181

(0 ... 100 V)

460/480 V

765 V - value in

C00181

(0 ... 100 V)

500 V

790 V - value in

C00181

(0 ... 100 V)