C00018 | chopper frequency, C00022 | maximum current, C00034 | config. analog input 1 – Lenze E94ARNE Regenerative power supply User Manual

Page 276: C00050 | output power (dc), C00051 | mains frequency, C00052 | mains voltage, When, C00034, C00050, C00051

Advertising
background image

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00018

276

L

EDS94ARNExxxx EN 2.3 - 06/2014

C00018

C00022

C00034

C00050

C00051

C00052

Parameter | Name:

C00018 | Chopper frequency

Data type: UNSIGNED_32

Index: 24557

d

= 5FED

h

Selection list

(Lenze setting printed in bold)

Information

14 1 kHz fixed

Note:

This parameter is only effective in closed-loop operation

(in preparation).

15 2 kHz fixed
16 4 kHz fixed
17 8 kHz fixed
21 2 kHz variable
22 4 kHz variable
23 8 kHz variable

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00022 | Maximum current

Data type: UNSIGNED_32

Index: 24553

d

= 5FE9

h

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A

21474836.47 0.00 A

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100

Parameter | Name:

C00034 | Config. analog input 1

Data type: UNSIGNED_32

Index: 24541

d

= 5FDD

h

Selection list

(Lenze setting printed in bold)

0 -10 ... +10 V
1 -20...-4 mA, +4...+20 mA
2 -20 ... +20 mA

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00050 | Output power (DC)

Data type: INTEGER_32

Index: 24525

d

= 5FCD

h

Display range

(min. value | unit | max. value)

-1000.0

kW

1000.0

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00051 | Mains frequency

Data type: INTEGER_32

Index: 24524

d

= 5FCC

h

Display range

(min. value | unit | max. value)

-800.0

Hz

800.0

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00052 | Mains voltage

Data type: UNSIGNED_32

Index: 24523

d

= 5FCB

h

Display range

(min. value | unit | max. value)

0

V

2147483647

Read access  Write access  CINH  PLC STOP  No transfer