9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

I-1800

Communication parameter for the transmission of process data via TPDO1

[6-17] Assignment of the data telegram

Procedure for changing the identifier:

1. Deactivate the identifier (set bit 31 to "1").
2. Change the identifier.
3. Activate the identifier (set bit 31 to "0").

Index:

I-1800

Name:

TPDO1 communication parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

5

- (read access only)

ro

U8

1: COB-ID used by TPDO

0x180 + node ID

0

4294967295 rw

U32

2: Transmission type

254

0

255 rw

U8

3: Inhibit time

0 ms

0

0.1 ms

65535 rw

U16

4: Reserved

-

- (reserved, read or write access results in the error

message 0x06090011)

rw

U8

5: Event timer

0 ms

0

ms

65535 rw

U16

Subindex

Meaning

Lenze code

1

Identifier TPDO1

• The basic setting corresponds to the "Predefined

Connection Set": identifier = 0x180 + node ID

C00320/1

2

TPDO transmission type according to DS301 V4.02

Transmission type ( 113)

C00322/1

3

Minimum time interval between the transmission of

two identical TPDOs (see DS301 V4.02).

C00324/1

5

Cycle time for the transmission of PDOs with

transmission type "254".

C00356/1

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

0/1

0/1

Extended identifier*

11-bit identifier

* The extended identifier is not supported - bits 11 ... 29 must be set to "0".

Bit

Setting

Bit 30

0 RTR to this PDO possible (Lenze).
1 RTR to this PDO not possible (cannot be set).

Bit 31

0 PDO is active.
1 PDO is not active.