EDS94ARNExxxx EN 2.3 - 06/2014

L

321

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00618

C00618

C00625

C00635

C00636

C00637

Parameter | Name:

C00618 | No. of CRC cycles

Data type: UNSIGNED_32

Index: 23957

d

= 5D95

h

Display range

(min. value | unit | max. value)

0

4294967295

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00625 | CAN behaviour in case of fault

Data type: UNSIGNED_8

Index: 23950

d

= 5D8E

h

Mapping of the CANopen object

I-1029

(see DS301 V4.02)

"CAN on board" system bus

Selection list

(Lenze setting printed in bold)

0 State pre-operational
1 No state change
2 State stopped

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00635 | Resp to new firmw. standard dev.

Data type: UNSIGNED_32

Index: 23940

d

= 5D84

h

Selection list

(Lenze setting printed in bold)

1 Fault
6 Information
5 Warning
4 Warning locked
0 No response

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00636 | Resp. to new module in MXI1

Data type: UNSIGNED_32

Index: 23939

d

= 5D83

h

Selection list

(Lenze setting printed in bold)

1 Fault
6 Information
5 Warning
4 Warning locked
0 No response

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00637 | Resp. to new module in MXI2

Data type: UNSIGNED_32

Index: 23938

d

= 5D82

h

Selection list

(Lenze setting printed in bold)

1 Fault
6 Information
5 Warning
4 Warning locked
0 No response

Read access  Write access  CINH  PLC STOP  No transfer