21 reset transmitted energy, Reset transmitted energy – Lenze E94ARNE Regenerative power supply User Manual

Page 61

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

61

9400 regenerative power supply module | Parameter setting

Device interface

Device commands

4.1.21

Reset transmitted energy

This function is available from software version V2.0 onwards!

The

C00002

= "65: Reset transmitted energy" device command serves to reset the value

displayed in

C00145/1

to zero.

Display of output and regenerated energy

( 88)

Possible status displays for this device command

Related device commands

Reset regenerated energy

( 62)

Status (

C00003

)

Meaning

4293890 Device command in process

4259840 Device command executed successfully

4259841 General fault