3 masking of tpdos for event control, 4 data reception monitoring of rpdos, Masking of tpdos for event control – Lenze E94ARNE Regenerative power supply User Manual

Page 114: Data reception monitoring of rpdos

Advertising
background image

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Process data transfer

114

L

EDS94ARNExxxx EN 2.3 - 06/2014

6.6.3

Masking of TPDOs for event control

For TPDO1 ... TPDO4, a mask can be parameterised for each byte. If event-controlled

transmission is selected for a PDO, only the masked bits are evaluated.

Mask "0x0" means that no bit of the corresponding byte activates PDO transmission.

Mask "0xff" means that each bit of the corresponding byte can activate PDO

transmission.

Short overview: parameters for masking the TPDOs

6.6.4

Data reception monitoring of RPDOs

For each of the RPDOs 1 ... 4 a monitoring time can be set, within which the RPDO must

arrive. If the RPDO is not received within the monitoring time or with the configured sync,

the response parameterised for the respective RPDO is triggered.

Short overview: parameters for RPDO monitoring

Parameter

Information

Lenze setting

C00311/1...8

CAN TPDO1 mask byte x

0x00

C00312/1...8

CAN TPDO2 mask byte x

0x00

C00313/1...8

CAN TPDO3 mask byte x

0x00

C00314/1...8

CAN TPDO4 mask byte x

0x00

Parameter

Information

Lenze setting

Value Unit

C00357/1...4

CAN RPDOx monitoring time

3000 ms

C00591/1...4

Resp. to CAN-RPDOx error

No response