9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00878

324

L

EDS94ARNExxxx EN 2.3 - 06/2014

C00878

C01120

C01121

Parameter | Name:

C00878 | Status DCTRL control input

Data type: UNSIGNED_8

Index: 23697

d

= 5C91

h

Display range

(min. value | unit | max. value)

0

1

Subcodes

Information

C00878/1

States of control inputs

C00878/...
C00878/5

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C01120 | Sync source

Data type: UNSIGNED_8

Index: 23455

d

= 5B9F

h

Selection of the source for the synchronisation signals.

• Only one source at a time can synchronise the drive.

"CAN on board" system bus: sync telegram

Selection list

(Lenze setting printed in bold)

0 OFF
1 CAN on-board
2 CAN module
4 Module in MXI1
5 Module in MXI2
6 Digital input 1
7 Digital input 2
8 Digital input 3
9 Digital input 4

10 Digital input 5
11 Digital input 6
12 Digital input 7
13 Digital input 8

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C01121 | SYNC cycle time

Data type: UNSIGNED_32

Index: 23454

d

= 5B9E

h

Time with which the phase-locking loop (PLL) in the regenerative power supply module awaits the synchronisation

signals.

• The time set must be compatible to the cycle of the respective synchronisation source.

Note: In case that the synchronisation is carried out via the system bus (CANopen), only integer multiples of 1000 μs

make sense for the setting.

Example: For the system bus the interval between two synchronisation signals has been set with 2 ms. If the system

bus is to be used as synchronisation source, a synchronisation cycle of 2000 μs has to be set in C01121.

"CAN on board" system bus: sync telegram

Setting range

(min. value | unit | max. value)

Lenze setting

250

μs

20000 1000 μs

Read access  Write access  CINH  PLC STOP  No transfer