9400 regenerative power supply module | Parameter setting

Regenerative power supply module application

Parameterising the brake chopper/brake resistor

22

L

EDS94ARNExxxx EN 2.3 - 06/2014

3.1

Parameterising the brake chopper/brake resistor

The regenerative power supply module is equipped with an integrated brake transistor.

The required brake resistor has to be connected externally (see mounting instructions/

hardware manual).

The rated values for the brake transistor are listed in the Hardware Manual, chapter

"Rated data".

Stop!

If the connected brake resistor has a lower resistance than the parameterised

brake resistor, the brake transistor may be damaged!
The brake resistor can be thermally overloaded. Carry out protective measures

suitable for the system, e.g.:
• Parameterisation of an error response in

C00574

and evaluation of the

parameterised error message in the application or machine control.

I2t

utilisation of brake resistor

( 27)

• External wiring using the temperature contact on the brake resistor (e.g.

interruption of the supply via mains contactor and activation of the

mechanical brakes).