9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

158

L

EDS94ARNExxxx EN 2.3 - 06/2014

Example

Parameter data channel 2 of the controller with node address 4 is to be activated.

For this purpose, bit 31 must be set to "0" (≡ "SDO is valid") in the subindexes 1 and 2 of

the

I-1201

object.

The two "write request" commands must be sent from the master to the nodes via the

basic SDO channel.

Calculation of the identifiers

Identifier (COB-ID) = basic identifier + node address (node ID)

Basic identifier SDO2 from the master to the drive: 1600 (0x640)

Identifier = 0x640 + 0x4 = 0x644

Basic identifier SDO2 from the drive to the master: 1472 (0x5C0)

Identifier = 0x5C0 + 0x4 = 0x5C4

Resulting data (data 1 ... data 4)

[6-11] Assignment of the data telegram for subindex 1

[6-12] Assignment of the data telegram for subindex 2

Assignment of the user data

[6-13] Assignment of the user data for writing to subindex 1

[6-14] Assignment of the user data for writing to subindex 2

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

0

0

Extended identifier = 0

11-bit identifier = 0x644

0x00

0x00

0x06

0x44

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

0

0

Extended identifier = 0

11-bit identifier = 0x5C4

0x00

0x00

0x05

0xC4

1st byte

2nd byte

3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x23

0x01

0x12

0x01

0x44

0x06

0x00

0x00

1st byte

2nd byte

3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x23

0x01

0x12

0x02

0xC4

0x05

0x00

0x00