3 led status displays for the system bus, Led status displays for the system bus – Lenze E94ARNE Regenerative power supply User Manual

Page 103

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

103

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

LED status displays for the system bus

6.3

LED status displays for the system bus

The two upper LEDs "CAN-RUN" and "CAN-ERR" on the front panel of the device indicate

the CANopen state and signal CANopen errors.

[6-2]

LED status displays CAN-RUN and CAN-ERR

The meaning is given in the below table:

CAN-RUN

CAN-ERR

LED status display

Meaning

CAN-RUN

CAN-ERR

CANopen state

CANopen error

Only CAN-ERR lit

-

Bus off

CAN-RUN and CAN-ERR flicker

Automatic detection of baud rate is active.

CAN-RUN blinks every 0.2 s | CAN-ERR is off

Pre-operational

-

CAN-RUN blinks every 0.2 s | CAN-ERR blinks once, 1 s off

Warning limit reached

CAN-RUN blinks every 0.2 s | CAN-ERR blinks twice, 1 s off

Node guard event

Only CAN-RUN lit

Operational

-

CAN-RUN lit | CAN-ERR blinks once, 1 s off

Warning limit reached

CAN-RUN lit | CAN-ERR blinks twice, 1 s off

Node guard event

CAN-RUN lit | CAN-ERR blinks 3 times, 1 s off

Sync message error

CAN-RUN blinks every 1 s | CAN-ERR is off

Stopped

-

CAN-RUN blinks every 1 s | CAN-ERR blinks once, 1 s off

Warning limit reached

CAN-RUN blinks every 1 s | CAN-ERR blinks twice, 1 s off

Node guard event