0x00b00008, 0x00b00006, 0x00b00007 – Lenze E94ARNE Regenerative power supply User Manual

Page 253: 0x00b10000, Diagnostics & fault analysis error messages

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

253

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

CAN module (MXI2) RPDO7: Telegram not received or faulty [0x00b00006]

CAN module (MXI2) RPDO8: Telegram not received or faulty [0x00b00007]

CAN module (MXI2) PDO manager: Faulty configuration [0x00b00008]

CAN module (MXI2) SDO server: Faulty configuration [0x00b10000]

Response (Lenze setting printed in bold)

Setting:

C14591/7

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 7

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C14591/8

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 8

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN-PDO

configuration error

• Faulty project download.

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Mapping variables have incorrect CANopen indexes

according to DS405.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: A

configuration error has occurred in the CAN SDP server.

• Faulty project download.

• Invalid SDO server settings according to DS301V402

in the Engineer or PLC Designer.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.