9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

I-1005

This object serves to activate the generation of sync telegrams and to change the value of

the identifier.

This object is related to the Lenze codes

C00367

and

C00368

.

Generating sync telegrams
For the generation of sync telegrams, bit 30 (see below) must be set to "1". The time

interval between the sync telegrams can be set with the

I-1006

object.

Changing the identifier
In the Lenze setting (and in accordance with the CANopen specification), the value 0x80 is

entered in the 11-bit identifier for the reception of PDOs. This means that all modules are

by default set to the same sync telegram.

If sync telegrams are only to be received by certain communication modules, their

identifiers can be entered with values up to and including 0x07FF.

The identifier may only be changed if the communication module does not send any

sync telegrams (bit 30 = "0").

Procedure for changing the identifier:
– Deactivate the identifier (set bit 30 to "0").
– Change the identifier.
– Activate the identifier (set bit 30 to "1").

[6-2]

Assignment of the data telegram

Index:

I-1005

Name:

COB-ID SYNC message

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: COB-ID SYNC message

0x0000 0080

OR

0x8000 0080

0

4294967295 rw

U32

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

x

0/1

Extended identifier*

11-bit identifier

* The extended identifier is not supported - bits 11 ... 29 must be set to "0".