9400 regenerative power supply module | Parameter setting

Internal interfaces

LS_LineInterface - line interface

9.6

LS_LineInterface - line interface

The LS_LineInterface system block provides the internal interfaces for the line interface in

the function block editor.

Inputs

Outputs

Identifier

Data type

Information/possible settings

LI_bChopperTurnOn

BOOL

Activate brake chopper

TRUE Activate brake chopper.

Identifier

Data type

Value/meaning

LI_dnActualDCBusVoltage_n

DINT

Current DC-bus voltage in [%]

• 100 % ≡ 1000 V

LI_dnActualLineCurrent_n

DINT

Current mains current in [%]

• 100 % ≡ I

max_device

(

C00789

)

LI_dnActualLineVoltage_n

DINT

Current mains voltage in [%]

• 100 % ≡ 1000 V

LI_dnActualPower_w

DINT

Current power in [W]

LI_dnThermalLoadDevice_n

DINT

Thermal device utilisation in [%]

• Current result of the Ixt calculation.

• Display in

C00064

Monitoring the device utilisation ( 86)

LI_dnThermalLoadFilter_n

DINT

Thermal filter utilisation in [%]

LI_bDeviceOverloadWarning

BOOL

Status signal "Device overload"

TRUE The monitoring for device overload protection has responded.

LS_LineInterface

LI_dnActualBusVoltage_n

LI_bChopperTurnOn

LI_bOperational

LI_dnActualLineCurrent_n

LI_dnActualLineVoltage_n

LI_dnActualPower_w

LI_dnThermalLoadDevice_n

LI_bDeviceOverloadWarning

LI_bMainsVoltageOK

LI_dnThermalLoadFilter_n

LI_bFilterOverloadWarning

LI_bLimitationActive

LI_bRegenActive

LI_bChopperIsActive

LI_bFilterOvertemperature

LI_bChopperOffByTrouble