EDS94ARNExxxx EN 2.3 - 06/2014

L

263

9400 regenerative power supply module | Parameter setting

Internal interfaces

LS_LineInterface - line interface

LI_bChopperOffByTrouble

BOOL

From V2.0 onwards

Status signal "Brake chopper inhibited due to too high I2t utilisation"

TRUE The brake chopper is inhibited because the I2t utilisation is too high.

• Monitoring of the brake resistor's I2t utilisation has triggered the

parameterised error response "Brake chopper inhibited".

I2t

utilisation of brake resistor ( 27)

TRUEFALSE Pulse inhibit of the brake chopper is deactivated again because the

corresponding trigger threshold for I2t monitoring has been fallen

below by 5 %.

LI_bFilterOvertemperature

BOOL

From V2.0 onwards

Status signal "Filter temperature too high"

TRUE Monitoring of the filter temperature has responded:

• Temperature > 155 °C and

C00583

≠ "no response"

- or -

• open circuit sensor and

C00594

≠ "no response"

Identifier

Data type

Value/meaning