9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

I-1A02

The object I-1A02 serves to transmit parameter data via the TPDO3.

For the assignment of the data telegram see object

I-1A00

.

I-1A03

The object I-1A03 serves to transmit parameter data via the TPDO4.

For the assignment of the data telegram see object

I-1A00

.

Index:

I-1A02

Name:

TPDO3 mapping parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Number of mapped application

objects in PDO

0

0

8 rw

U8

1 ... 8: Application object 1 ... 8

0

0

4294967295 rw

U32

Subindex

Meaning

0

Number of mapped objects

1 ... 8

Mapping entries 1 ... 8 for TPDO3

Index:

I-1A03

Name:

TPDO4 mapping parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Number of mapped application

objects in PDO

0

0

8 rw

U8

1 ... 8: Application object 1 ... 8

0

0

4294967295 rw

U32

Subindex

Meaning

0

Number of mapped objects

1 ... 8

Mapping entries 1 ... 8 for TPDO4