Diagnostics & fault analysis

Error messages

Brake resistor: I²xt overload [0x007b001d]

Brake transistor: Overcurrent [0x007b0021]

Failure of mains phase L1 [0x007b002d]

Failure of mains phase L2 [0x007b002e]

Failure of mains phase L3 [0x007b002f]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Too frequent and too long brake operations.

• Check drive dimensioning.

• Check parameter setting (

C00129

,

C00130

,

C00131

).

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Brake chopper short circuit/earth fault detected.

Check brake chopper cable and brake resistor.

Response (Lenze setting printed in bold)

None  System fault  Fault Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Interruption of phase L1 of the mains cable.

Up to software version V02.00.19

a fault is reported if

a mains phase failure occurs.

From software version V02.00.20

a trouble is reported

for mains phase failures < 500 ms. If the mains phase

failure is pending longer than 500 ms, the device

changes to the "Fault" status.

If the fault is pending longer and the device reports a

fault, check the cabling between the regenerative power

supply module and the mains.

Response (Lenze setting printed in bold)

None  System fault  Fault Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Interruption of phase L2 of the mains cable.

Up to software version V02.00.19

a fault is reported if

a mains phase failure occurs.

From software version V02.00.20

a trouble is reported

for mains phase failures < 500 ms. If the mains phase

failure is pending longer than 500 ms, the device

changes to the "Fault" status.

If the fault is pending longer and the device reports a

fault, check the cabling between the regenerative power

supply module and the mains.

Response (Lenze setting printed in bold)

None  System fault  Fault Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Interruption of phase L3 of the mains cable.

Up to software version V02.00.19

a fault is reported if

a mains phase failure occurs.

From software version V02.00.20

a trouble is reported

for mains phase failures < 500 ms. If the mains phase

failure is pending longer than 500 ms, the device

changes to the "Fault" status.

If the fault is pending longer and the device reports a

fault, check the cabling between the regenerative power

supply module and the mains.