C00320 | can tpdox identifier, C00321 | can rpdox identifier, C00321/1 – Lenze E94ARNE Regenerative power supply User Manual

Page 295: C00320/1, C00321/2, C00320/2, C00321/3, C00320/3, C00321/4, C00320/4

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

295

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00320

C00320

C00321

Parameter | Name:

C00320 | CAN TPDOx identifier

Data type: BITFIELD_32

Index: 24255

d

= 5EBF

h

Identifier for TPDO1 ... TPDO4

• If bit 31 is set (0x8nnnnnnn), the TPDO is deactivated.

• The basic setting is according to the "Predefined Connection Set".

• Mapping of CANopen objects

I-1800/1

...

I-1803/1

(see DS301 V4.02).

"CAN on board" system bus

Value is bit-coded:

Information

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: PDO invalid

... ...

Bit 31 PDO invalid

Subcodes

Lenze setting

Information

C00320/1

0x00000181

Identifier TPDO1

• After a node address change and CAN reset node, the

value 0x180 + node address will be set by default.

C00320/2

0x00000281

Identifier TPDO2

• After a node address change and CAN reset node, the

value 0x280 + node address will be set by default.

C00320/3

0x00000381

Identifier TPDO3

• After a node address change and CAN reset node, the

value 0x380 + node address will be set by default.

C00320/4

0x00000481

Identifier TPDO4

• After a node address change and CAN reset node, the

value 0x480 + node address will be set by default.

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00321 | CAN RPDOx identifier

Data type: BITFIELD_32

Index: 24254

d

= 5EBE

h

Identifier for RPDO1 ... RPDO4

• If bit 31 is set (0x8nnnnnnn), the RPDO is deactivated.

• The basic setting is according to the "Predefined Connection Set".

• Mapping of CANopen objects

I-1400/1

...

I-1403/1

(see DS301 V4.02).

"CAN on board" system bus

Value is bit-coded:

Information

Bit 0 COB-ID bit 0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: PDO invalid

... ...

Bit 31 PDO invalid

Subcodes

Lenze setting

Information

C00321/1

0x00000201

Identifier RPDO1

• After a node address change and CAN reset node, the

value 0x200 + node address will be set by default.

C00321/2

0x00000301

Identifier RPDO2

• After a node address change and CAN reset node, the

value 0x300 + node address will be set by default.

C00321/3

0x00000401

Identifier RPDO3

• After a node address change and CAN reset node, the

value 0x400 + node address will be set by default.

C00321/4

0x00000501

Identifier RPDO4

• After a node address change and CAN reset node, the

value 0x500 + node address will be set by default.

Read access  Write access  CINH  PLC STOP  No transfer