9400 regenerative power supply module | Parameter setting

Oscilloscope

Function description

7.2

Function description

Establish an online connection to the regenerative power supply module and use the

oscilloscope user interface of the »Engineer« to select the trigger condition, the sample

rate and the variables to be recorded.
When the measurement is started, the set parameters are transferred to the regenerative

power supply module and checked. If invalid settings are found, the oscilloscope sends an

error. Otherwise, the measurement is started.
With an online connection, the measured data now stored in the regenerative power

supply module are transferred to the »Engineer« and graphically represented on the

oscilloscope user interface as soon as the measurement has been completed.

Recording variable values
The operating system calls the oscilloscope in fixed 1 ms-cycles, i.e. the oscilloscope can

record variable values with a sample rate of max. 1 kHz.

Recording system variable values of the internal control
Unlike the variables declared in the application, the system variables of the internal control

can also be recorded with a sample rate higher than 1 kHz.

Recording task-related I/O variable values
When selecting the variables to be measured, it is possible to indicate a task reference for

these variables. If the behaviour of a certain task is to be examined, you can indicate the

task reference to exactly record the values valid for the task run-time.

The variable values are recorded during the process output image generation of the

task.

Note!

In the control system recordings with a time-based resolution of 31.25 μs and

125 μs are not possible!
The system variables of the internal control have a cycle offset of 2 ... 3 ms with

respect to all other variable values!