9400 regenerative power supply module | Parameter setting

Commissioning

Short setup

2.1.4

Controlling the regenerative power supply module via terminals

If the regenerative power supply module is enabled, the application can be controlled via

the digital inputs and/or MotionBus (if it is integrated in a network).

Terminal assignment of digital inputs

Tip!
Detailed information on device applications can be found in the chapter

"

Regenerative power supply module application

".

( 21)

Note!

The regenerative power supply module still remains inhibited via the controller

enable terminal (RFR) if this terminal is set to LOW level.
Please note that the regenerative power supply module will only be enabled if all

sources for controller inhibit are reset!
• The sources or trip elements that are active for controller inhibit are displayed

in a bit-coded manner in

C00158

.

Terminal

Assignment (Lenze setting)

X5

RFR

Controller enable

DI1

Inhibit regenerative feedback

• Function also possible via bit 01 of control word 1.

DI2

Activate brake chopper

• Function also possible via bit 02 of control word 1.

DI3

Reset (acknowledge) error

• A pending error message can be reset (acknowledged) by a LOW-HIGH edge if the cause of

the error message has been eliminated.

• Function also possible via bit 07 of control word 1.