C00003 | device command status, C00004 | service password, C00005 | application selection – Lenze E94ARNE Regenerative power supply User Manual

Page 275: C00006 | selected control scheme, C00007 | active application, C00003, That the device command has, The meaning of the status display in, Can be obtained from the, C00005

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

275

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00003

C00003

C00004

C00005

C00006

C00007

Parameter | Name:

C00003 | Device command status

Data type: UNSIGNED_32

Index: 24572

d

= 5FFC

h

Display of the number/state of the device command last executed (

C00002

).

• The number of the command stands in the upper 16 bits (for the meaning of the number, see code

C00002

).

• The result of the command stands in the lower 16 bits.

Note:

Before switching off the supply voltage after a device command has been executed, check via the status display in

C00003

that the device command has been executed successfully!

The meaning of the status display in

C00003

can be obtained from the subchapter for the corresponding device

command in the "

Device commands

" chapter.

Display range

(min. value | unit | max. value)

0

4294967295

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00004 | Service password

Data type: UNSIGNED_32

Index: 24571

d

= 5FFB

h

Service code to unlock protected device commands (

C00002

).

Setting range

(min. value | unit | max. value)

Lenze setting

0

4294967295 0

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00005 | Application selection

Data type: INTEGER_32

Index: 24570

d

= 5FFA

h

Selecting the application

• Use the device command

C00002

="5" to activate the selected application.

Setting range

(min. value | unit | max. value)

Lenze setting

-1

16 0

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00006 | Selected control scheme

Data type: UNSIGNED_8

Index: 24569

d

= 5FF9

h

Selection list

(display only)

1 Modus: closed loop control
2 Modus: open loop control

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00007 | Active application

Data type: INTEGER_32

Index: 24568

d

= 5FF8

h

Display range

(min. value | unit | max. value)

-2147483648

2147483647

Read access  Write access  CINH  PLC STOP  No transfer