Parameter set: version conflict [0x00900007, No parameters for module in mxi1 [0x0090000a, No parameters for module in mxi2 [0x0090000b – Lenze E94ARNE Regenerative power supply User Manual

Page 241: Mains voltage is switched on [0x00910000, Mains voltage is switched off [0x00910001, 0x00910001, 0x00910000, 0x0090000a, 0x0090000b, 0x00900009

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

241

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

Parameter set: Version conflict [0x00900007]

Parameter set: Type of standard device has been changed [0x00900009]

No parameters for module in MXI1 [0x0090000a]

No parameters for module in MXI2 [0x0090000b]

Mains voltage is switched on [0x00910000]

Mains voltage is switched off [0x00910001]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The parameter set version on the memory module is not

compatible with the firmware of the regenerative power

supply module.

Transfer parameter set from the Engineer to the

regenerative power supply module and save it with

C00002

="11".

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The firmware has loaded a parameter set the type code

of which does not correspond to the type code of the

regenerative power supply module.

Load a suitable parameter set.

Response (Lenze setting printed in bold)

Setting:

C00615/2

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The parameter set contains no parameters for the

module inserted in MXI1.

Integrate the module inserted in MXI1 into the Engineer

project and then transmit the parameter set to the

regenerative power supply module again.

Response (Lenze setting printed in bold)

Setting:

C00615/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The parameter set contains no parameters for the

module inserted in MXI2.

Integrate the module inserted in MXI2 into the Engineer

project and then transmit the parameter set to the

regenerative power supply module again.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Mains voltage has been switched on.

- (Information only)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Mains voltage has been switched off.

- (Information only)