Error in control configuration [0x006a0017, 0x006f0000, 0x006a0017 – Lenze E94ARNE Regenerative power supply User Manual

Page 220: 0x006a0015, 0x006a0016, Diagnostics & fault analysis error messages

Advertising
background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

220

L

EDS94ARNExxxx EN 2.3 - 06/2014

PDO mapping (MXI1): Faulty configuration [0x006a0015]

PDO mapping (MXI2): Faulty configuration [0x006a0016]

Error in control configuration [0x006a0017]

Control card: Supply voltage (24 V DC) too low [0x006f0000]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Incorrectly

configured process data mapping.

• The corresponding PDO channel is not installed, since,

for instance, no communication module has been

selected for the module slot MXI1 in the Engineer

project.

• The communication module selected for the module

slot MXI1 in the Engineer project does not support

PDO mapping.

• The mapping information transferred to the

regenerative power supply module is incorrect.

• Integrate suitable communication module into the

Engineer project for the module slot MXI1.

• Check the configuration of the network. Then

recompile the project and transfer it to the

regenerative power supply module.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: Incorrectly

configured process data mapping.

• The corresponding PDO channel is not installed, since,

for instance, no communication module has been

selected for the module slot MXI2 in the Engineer

project.

• The communication module selected for the module

slot MXI2 in the Engineer project does not support

PDO mapping.

• The mapping information transferred to the

regenerative power supply module is incorrect.

• Integrate suitable communication module into the

Engineer project for the module slot MXI2.

• Check the configuration of the network. Then

recompile the project and transfer it to the

regenerative power supply module.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid control configuration has occurred.

Load another application.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

External 24V voltage supply of the control card is lower

than 18 V.

Check external supply voltage.

• If the external supply voltage is available and the

error message still occurs, contact Lenze.