Connecting the Kinetix 6200 and Kinetix 6500 Drive System

Chapter 5

This example applies to a common-bus follower IAM power module.

Figure 56 - IAM Power Module (IPD connector)

Table 55 - Input Power (IPD) Connections

Table 56 - Termination Specifications

ATTENTION: Make sure the common-bus power connections are correct when
wiring the IPD connector plug and that the plug is fully engaged in the module
connector. Incorrect wiring/polarity or loose wiring can cause explosion or
damage to equipment.

DC-

DC+

L3

L2

L1

1 2 3 4 5 6

Bulletin 2094
IAM Power Module, Top View

IPD Connector
(IAM or follower IAM module)

IPD Pin

Signal

6

N.C.

5

N.C.

4

N.C.

3

2

DC+

1

DC-

IMPORTANT

Do not connect three-phase input power to the common-bus follower IAM
module.

IAM Module Cat. No.

Input VAC

Recommended
Wire Size
mm

2

(AWG)

Strip Length
mm (in.)

Torque Value
N•m (lb•in)

2094-BC01-Mxx-M
2094-BC02-M02-M

460V AC

2.5 (14)

10 (0.38)

1.2…1.5
(10.6…13.2)

2094-BC04-M03-M

6 (10)

16 (0.63)

2.4…3.0
(21.6…26.5)

2094-BC07-M05-M

30 (3)