Input Power Cycle Capability

The power cycle capability is inversely proportional to the system capacitance
(including DC bus follower), but cannot exceed 2 contactor cycles per minute
with up to 4 axes or 1 contactor cycle per minute with 5…8 axes.

The cycle capability also depends on the converter power rating and the total
system capacitance. Refer to Appendix C on

page 267

to calculate total system

capacitance.

Table 30 - Maximum Input Power Cycling Specifications (460V)

For example, in a 4 axis system with a 2094-BC02-M02-M IAM power module
and 2,000 μF total capacitance, the calculated capability is 0.52 x 10,000/2000 =
2.6 cycles per minute. However, this value is reduced to 2.0 by the 4 axes per
system limitation.

Attribute

2094-BC01-MP5-M,
2094-BC01-M01-M

2094-BC02-M02-M

2094-BC04-M03-M

2094-BC07-M05-M

Main AC input power cycling
(cycles per minute for 10,000 μf)

0.12

0.52

2.15

4.30