Rockwell Automation Publication 2094-UM002E-EN-P - May 2012

93

Connecting the Kinetix 6200 and Kinetix 6500 Drive System

Chapter 5

Determine the Input Power
Configuration

Before wiring input power to your Kinetix 6200 or Kinetix 6500 system, you
must determine the type of input power you are connecting to. The IAM power
module is designed to operate in both grounded and ungrounded environments.

Grounded Power Configurations

The grounded (WYE) power configuration lets you ground your three-phase
power at a neutral point. This type of grounded power configuration is preferred.

Figure 47 - Grounded Power Configuration (WYE Secondary)

Refer to

Power Wiring Examples

beginning on

page 233

for input power

interconnect diagrams with and without the LIM module.

ATTENTION: When using a LIM module with your IAM power module, the VAC
LINE input power must come from a grounded configuration (refer to the figure
below).
When not using a LIM module with your IAM power module, ungrounded
configurations are permitted, but you must set the jumper to prevent high
electrostatic build-up.
Refer to Setting the Ground Jumper in Ungrounded Power Configurations on

page 97

for more information.

L3

L2

L1

1 2

DC-

DC+

L3

L2

L1

CONT EN-

CONT EN+

CTRL 2

CTRL 1

1 2

1 2 3 4 5 6

W

V
U

MBRK -

MBRK +

COM

PWR

DBRK -

DBRK +

1 2 3 4

1 2 3 4 5 6

Transformer

Three-phase

Input VAC

Phase Ground

Transformer (WYE) Secondary

Bonded Cabinet

Ground

Ground Grid or

Power Distribution Ground

Connect to power rail
ground stud.

Three-phase

AC Line Filter

Input Fusing

M1

Contactor

Bulletin 2094

IAM Power Module, Top View