Enclosure Selection

This example is provided to assist you in sizing an enclosure for your Bulletin
2094 drive system. The example system consists of these components:

6-axis Bulletin 2094 servo drive system
Line Interface Module (LIM)
ControlLogix chassis and modules (controller)

Size the Bulletin 2094 servo drive and LIM module and use the results to predict
the amount of heat dissipated into the enclosure. You will also need heat
dissipation data from other equipment inside the enclosure (such as the
ControlLogix controller). Once the total amount of heat dissipation (in watts) is
known, you can calculate the minimum enclosure size.

Table 6 - Bulletin 2094 System Heat Dissipation Example

Enclosure Component

Description

Loading

(1)

Heat Dissipation

(1)

watts

2094-BC02-M02-M

Integrated axis module (IAM),
400/460V

15 kW (converter section)

20%

44

15 A (inverter section)

40%

72

2094-BM02-M

Axis module (AM), 400/460V, 15 A

60%

93

2094-BM02-M

Axis module (AM), 400/460V, 15 A

60%

93

2094-BM01-M

Axis module (AM), 400/460V, 9 A

40%

73

2094-BM01-M

Axis module (AM), 400/460V, 9 A

40%

73

2094-BM01-M

Axis module (AM), 400/460V, 9 A

20%

57

2094-BL25S

Line interface module (LIM), 400/460V, 25 A; 24V DC 20 A

100%

43

2094-PRS6

Power rail, 460V, 6 axis

N/A

0

2090-XB33-32

Resistive brake module (RBM), 33 A, 32

N/A

30

Total Kinetix 6200 and Kinetix 6500 system wattage

578

(1) To determine heat dissipation specifications for your drive system components, refer to