Planning the Kinetix 6200 and Kinetix 6500 Drive System Installation

Chapter 2

Observe these guidelines when the 2094-BL

xxS or 2094-XL75S-Cx LIM

module is used in the Bulletin 2094 system and mounted right of the drive with
the AC (EMC) line filter mounted behind the LIM module:

The clean zone (C) is to the left and beneath the Bulletin 2094 system

(gray wireway).

The dirty zone (D) is to the right and above the Bulletin 2094 system, and

above and below the LIM module (black wireway).

The very dirty zone (VD) is from the filter output to drive. Shielded cable

is required on the EMC filter (load side) and the braided shield attached
to the clamp (when provided).

The sercos fiber-optic cables are immune to electrical noise, but due to

their delicate nature, route them in the clean zone. Ethernet cables are
noise sensitive and belong in the clean zone.

Figure 15 - Noise Zones (EMC filter behind LIM module)

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway.
(2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the

System Design for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

(3) Only the 2094-ALxxS and 2094-XL75S-Cx LIM modules are compatible with the 2094 mounting brackets. The 2094-BLxxS, 2094-

AL09, and 2094-BL02 LIM modules are not compatible.

C

D

D

D

VD

C

VD

D

D

D

LIM

PRS

PR

LIM

Line Interface Module

Clean Wireway

Dirty Wireway

Motor Power Cables

2094 Mounting

(3)

Brackets x2

VAC Load

VAC Line

AC (EMC)
Line Filter

Control VAC,
Auxiliary VAC,
and 24V DC Brake

LIM
I/O

Very Dirty Filter/IAM Connections

Segregated (not in wireway)

No sensitive

(2)

equipment within

150 mm (6.0 in.).

I/O

(1)

, Feedback, and

Ethernet Cables

Route 24V DC switched signals

in shielded cable.

Route encoder, analog, registration, and communication
signals in shielded cables.

I/O

(1)

and Safety Cables

Fiber-optic Cable