272

Rockwell Automation Publication 2094-UM002E-EN-P - May 2012

Appendix D

Changing the Default IDN Parameter Values

Use this flowchart to determine if changing your default configuration is
required.

Figure 117 - Configuration Flowchart

Change IDN Parameter
Values

In this section you follow the Configuration Flowchart on

page 272

to determine

if you need to use the sercos IDN Write instruction in RSLogix 5000 software to
change the IDN parameter values.

Read the Present IDN Parameter Value

Follow these steps to read the present IDN value.

1. Start your RSLogix 5000 software application program.
2. Configure a Message Configuration (MSG) instruction to read your

present IDN parameter values.

Read the present IDN default

parameter value by using the sercos

IDN Read instruction.

Calculate/select the correct IDN value for

your application.

Does the

calculated/selected

IDN value match

the IDN Read

instruction value?

Change the IDN parameter value by

using the

sercos IDN Write instruction.

Parameters are already set correctly.

You do not need to change IDN

parameter values.

Start

No

Yes

page 272

page 274