Chapter 7

Configure and Start the Kinetix 6500 Drive System

4. Type 2.0 as the number of revolutions for the test or another number more

appropriate for your application.

5. Determine your need for a hardware enable input at IOD-41 on the I/O

connector.

Digital input 1 (IOD-41) is configured as Enable in RSLogix 5000
software by default. You may have changed that on

page 179

.

6. Apply Hardware Enable Input signal for the axis you are testing.

7. Click the desired tab (Marker/Motor Feedback/Motor and Feedback).

In this example, the Motor and Feedback test is chosen.

8. Click Start.

The RSLogix 5000 - Motor and Feedback Test dialog box opens. The Test
State is Executing.

When the test completes successfully, the Test State changes from
Executing to Passed.

This Test

Performs this Test

Marker

Verifies marker detection capability as you rotate the motor
shaft.

Motor Feedback

Verifies feedback connections are wired correctly as you rotate
the motor shaft.

Motor and Feedback

Verifies motor power and feedback connections are wired
correctly as you command the motor to rotate.

If Digital Input 1 is configured as

Then

Enable

Go to

step 6

.

Unassigned

Go to

step 7

.

ATTENTION: To avoid personal injury or damage to equipment, apply
24V ENABLE signal only to the axis you are testing.