Chapter 2

Planning the Kinetix 6200 and Kinetix 6500 Drive System Installation

Keep the DC common-bus cable (very dirty) segregated from all other cables
(not in a wireway) when the 2094-BL

xxS or 2094-XL75S-Cx LIM module is

used in a DC common-bus configuration and the follower IAM module is
mounted below the leader IAM module.

Figure 16 - Noise Zones (DC common bus)

(1) If drive system I/O cable contains (dirty) relay wires, route cable with LIM module I/O cable in dirty wireway.

(2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, refer to the

System Design for Control of Electrical Noise Reference Manual, publication

GMC-RM001

.

C

D

VD

D

D

D

VD

D

C

VD

D

D

D

D

D

D

C

C

Line Interface Module

Kinetix 6200 or
Kinetix 6500 System

Dirty Wireway

Clean Wireway

Motor Power Cables

VAC Line, AUX VAC Output, 24V

VAC Line

AC Line Filter

(required for CE)

VAC Load

Kinetix 6200 or
Kinetix 6500 System

Very Dirty Filter/IAM Connections

Segregated (not in wireway)

Very Dirty DC Bus Connections

Segregated (not in wireway)

Fiber-optic Cable

I/O

(1)

, Feedback, and

Ethernet Cables

Route 24V DC switched signals
in shielded cable.

Route encoder, analog, registration, and

communication signals in shielded cables.

I/O

(1)

and Safety Cables

I/O

(1)

, Feedback, and

Ethernet Cables

Fiber-optic Cable

No sensitive

(2)

equipment within

150 mm (6.0 in.).

No sensitive

(2)

equipment within

150 mm (6.0 in.).