Rockwell Automation Publication 2094-UM002E-EN-P - May 2012

31

Planning the Kinetix 6200 and Kinetix 6500 Drive System Installation

Chapter 2

Circuit Breaker and Fuse Specifications

While circuit breakers offer some convenience, there are limitations for their use.
Circuit breakers do not handle high current inrush as well as fuses.

Make sure the selected components are properly coordinated and meet
acceptable codes including any requirements for branch circuit protection.
Evaluation of the short-circuit available current is critical and must be kept below
the short-circuit current rating of the circuit breaker.

The following fuse examples and Allen-Bradley circuit breakers are
recommended for use with 2094-BC

xx-Mxx-M IAM power modules when the

Line Interface Module (LIM) is not used.

Refer to the Kinetix Servo Drives Technical Data, publication

GMC-TD003

, for

additional power specifications for your IAM power module.

IMPORTANT

LIM Module (catalog number 2094-BLxxS) provides branch circuit protection to the IAM power module. Follow all applicable
NEC and local codes.

IAM Module
Cat. No.

V AC Input Power

Control Input Power

DC Common Bus Fuse

Bussmann
Fuse

Allen-Bradley Circuit Breaker

Bussmann Fuse

(1)

Allen-Bradley

(2)

Circuit Breaker

Bussmann
Fuse

Ferraz Shawmut
Fuse

Disconnect

Magnetic
Contactor

2094-BC01-MP5-M

KTK-R-20 (20 A)

1492-SP3D300

140M-F8E-C32

FNQ-R-10 (10 A) or
FNQ-R-7.5 (7.5 A)

1492-SP2D060 or
1492-SP1D150

FWJ-20A14F

DCT20-2

2094-BC01-M01-M

2094-BC02-M02-M

KTK-R-30 (30 A)

1492-SP3D400

140M-F8E-C45

FWJ-40A

A70QS40-4

2094-BC04-M03-M

LPJ-45SP (45 A)

N/A

140U-H6C3-C50

FWJ-70A

A70QS70-4

2094-BC07-M05-M

LPJ-80SP (80 A)

140U-H6C3-C90

FWJ-125A

A70QS125-4

(1) Use FNQ-R-7.5 fuse for higher single-cycle inrush current capability. This is recommended when the continuous control power current exceeds 3.0 A.
(2) Use 1492-SP1D150 circuit breaker for higher single-cycle inrush current capability. This is recommended when the continuous control power current exceeds 3.0 A.