Shunt module status indicators – Rockwell Automation 2094-EN02D-M01-Sx Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drives User Manual User Manual
Page 210

210
Rockwell Automation Publication 2094-UM002E-EN-P - May 2012
Chapter 8
Troubleshooting the Kinetix 6200 and Kinetix 6500 Drive System
Table 90 - Safety Lock Status Indicator
Table 91 - Port 1 and Port 2 Ethernet Communication Status Indicators
Table 92 - Module and Network Status Indicators (EtherNet/IP control modules)
Shunt Module Status Indicators
Each of the shunt module status indicators provide specific troubleshooting
information.
Table 93 - General Shunt Module Troubleshooting
Condition
(1)
(1) This status indicator applies to only 2094-xx02x-M0x-S1 control modules.
Status
Off
No power or safety circuitry not configured.
Flashing amber
Safety circuitry configured, but not locked.
Steady amber
Safety circuitry locked.
Condition
Status
Off
No link partner present.
Flashing green
Link partner present, communication occurring.
Steady green
Link partner present, no communication occurring.
Condition
Status
Off
No power or no IP address defined.
Alternating green/red
Self-test mode (powerup diagnostics).
Flashing green
Standby (device not configured, or connection not
established.
Steady green
Normal operation. Device has at least one established
connection.
Flashing red
Recoverable minor fault or connection timeout.
Steady red
Non-recoverable major fault or duplicate IP address.
Module
Status
Under These Conditions
Shunt
Fault is latched.
Until fault condition is corrected and cleared.
Fault is cleared.
• Using MASR, MAFR, MGSR instructions or the HIM (red stop button).
• Only after the DC bus is discharged (bus status indicator is flashing).
• Drive must be configured with 2094-BSP2 shunt module or Bulletin 1394 external shunt module.
IAM/AM
Disabled (for DC bus regulation).
• When the 2094-BSP2 shunt module is used on a 230V system.
• When either 230V or 460V system is configured with a Bulletin 1394 external shunt module.
• When configured in Common-bus Follower mode.
Enabled to discharge the DC bus.
Drive (IAM or leader IAM module) three-phase power is removed.
Disabled from discharging the
DC bus.
When configured in Common-bus Follower mode.
IMPORTANT
Under some fault conditions, two reset commands may be required to clear
drive and shunt module faults.