Chapter 8

Troubleshooting the Kinetix 6200 and Kinetix 6500 Drive System

Table 90 - Safety Lock Status Indicator

Table 91 - Port 1 and Port 2 Ethernet Communication Status Indicators

Table 92 - Module and Network Status Indicators (EtherNet/IP control modules)

Shunt Module Status Indicators

Each of the shunt module status indicators provide specific troubleshooting
information.

Table 93 - General Shunt Module Troubleshooting

Condition

(1)

(1) This status indicator applies to only 2094-xx02x-M0x-S1 control modules.

Status

Off

No power or safety circuitry not configured.

Flashing amber

Safety circuitry configured, but not locked.

Steady amber

Safety circuitry locked.

Condition

Status

Off

No link partner present.

Flashing green

Link partner present, communication occurring.

Steady green

Link partner present, no communication occurring.

Condition

Status

Off

No power or no IP address defined.

Alternating green/red

Self-test mode (powerup diagnostics).

Flashing green

Standby (device not configured, or connection not
established.

Steady green

Normal operation. Device has at least one established
connection.

Flashing red

Recoverable minor fault or connection timeout.

Steady red

Non-recoverable major fault or duplicate IP address.

Module

Status

Under These Conditions

Shunt

Fault is latched.

Until fault condition is corrected and cleared.

Fault is cleared.

Using MASR, MAFR, MGSR instructions or the HIM (red stop button).
Only after the DC bus is discharged (bus status indicator is flashing).
Drive must be configured with 2094-BSP2 shunt module or Bulletin 1394 external shunt module.

IAM/AM

Disabled (for DC bus regulation).

When the 2094-BSP2 shunt module is used on a 230V system.
When either 230V or 460V system is configured with a Bulletin 1394 external shunt module.
When configured in Common-bus Follower mode.

Enabled to discharge the DC bus.

Drive (IAM or leader IAM module) three-phase power is removed.

Disabled from discharging the
DC bus.

When configured in Common-bus Follower mode.

IMPORTANT

Under some fault conditions, two reset commands may be required to clear
drive and shunt module faults.