Chapter 3

Mounting the Kinetix 6200 and Kinetix 6500 Drive System

2. Determine the next available slot and module for mounting.

3. Hang the mounting bracket from the slot on the power rail.

4. Pivot module downward and align the guide pins on the power rail with

the guide pin holes in the back of the module.

ATTENTION: To avoid damage to the pins located on the back of each
IAM, AM, IPIM, shunt, and slot-filler module and to make sure that
module pins mate properly with the power rail, hang modules as
shown in

step 3

through

step 6

.

The power rail must be mounted vertically on the panel before hanging
modules on the power rail. Do not mount modules if the power rail is
horizontal.

Power Rail

IAM or AM Power Module, IPIM,
Shunt, or Slot-filler Module
(IAM power module is shown)

Slots for additional axis modules,

shunt module, or slot-filler modules.

Power Rail Slot

Mounting Bracket

Guide Pin
Holes

Power rail (side view)

in upright vertical position.

Guide Pins

Pivot module downward
and align with guide pins.

IAM or AM Power Module, IPIM,

Shunt, or Slot-filler Module, Side View

(IAM power module is shown)

IAM or AM Power Module, IPIM,

Shunt, or Slot-filler Module, Rear View

(AM power module is shown)