Noise Reduction Guidelines for Drive Accessories

Refer to this section when mounting an AC (EMC) line filter or external shunt
module for guidelines designed to reduce system failures caused by excessive
electrical noise.

AC Line Filters

Observe these guidelines when mounting your AC (EMC) line filter (refer to the
figure on

page 46

for an example):

Mount the AC line filter on the same panel as the Kinetix 6200 and

Kinetix 6500 drive and as close to the power rail as possible.

Good HF bonding to the panel is critical. For painted panels, refer to the

examples on

page 37

.

Segregate input and output wiring as far as possible.

IMPORTANT

CE test certification applies only to AC line filter and single power rail. Sharing a
line filter with multiple power rails may perform satisfactorily, but the user
takes legal responsibility.