Troubleshooting the Kinetix 6200 and Kinetix 6500 Drive System

Chapter 8

Table 94 - Bus Status Indicator

Table 95 - Temperature Fault Status Indicator

Table 96 - Shunt Fault Status Indicator

Table 97 - All Shunt Module Status Indicators

Bus Status Indicator

Status

Potential Cause

Possible Resolution

Flashing

Normal condition when control power is applied and bus voltage is less than 60V DC.

N/A

Steady Green

Normal condition when control power is applied and bus voltage is greater than 60V DC.

N/A

Off

Control power is not present.

Internal power supply failure.

Replace shunt module.

Over-Temp Fault
Indicator

Status

Potential Cause

Possible Resolution

Off

Normal condition.

N/A

Steady Red

Shunt module internal
temperature exceeds operating
temperature specification.

Shunt module fan failed.

Replace shunt module.

Shunt module temperature exceeds rating.

Wait for shunt module to cool.
Reset faults.
Verify IAM module bus regulator configuration.

External over temperature
condition.

External temperature switch is open.

Wait for shunt module to cool.
Reset faults.
Verify IAM module bus regulator configuration.

TS jumper is not present.

Install jumper.

Shunt Fault Indicator

Status

Potential Cause

Possible Resolution

Off

Normal condition

N/A

Steady Red

Shorted internal or external shunt
resistor.

Mis-wired shunt jumper or other short on RC
connector.

Correct mis-wire (shorted) condition.
If problem persists, replace shunt module.

Mis-wired (shorted) external shunt wiring.

Shunt Module Status
Indicator

Status

Potential Cause

Possible Resolution

Bus Status
Over-Temp Fault
Shunt Fault

All three status indicators flash
simultaneously.

Shunt module hardware failure.

Cycle power.
If problem persists, replace shunt module.